Comet M1322 - Ethernet Multilogger - thermo-hygro-CO2 meter with 2 MiniDIN and 2 Terminals
Comet M1322 - Ethernet Multilogger - thermo-hygro-CO2 meter with 2 MiniDIN and 2 Terminals Multilogger Data Loggers Comet Singapore Distributor, Supplier, Supply, Supplies | Mobicon-Remote Electronic Pte Ltd
Quantity
Download Files
https://www.cometsystem.com/pdf/m1322

code: M1322

Battery powered datalogger with built-in CO2 sensor and 4 universal inputs for measurement of temperature, humidity, 0-10V voltage, 0-20mA current, two-state signal and for counting pulses.
Multilogger can be installed permanently to Ethernet network or work as portable device.
Included is traceable calibration certificate in accordance with EN ISO/IEC17025.
The device is designed for measuring and recording temperature, humidity, CO2 (internal sensor) with adjustable recording intervals from 1 second to 24 hours.

Datalogger can be connected to Ethernet.
Then measured values can be viewed on a web browser, as well as stored and downloaded for later analysis.
  • on-line monitoring
  • recording of data
  • alarm warnings

INCLUDED IN DELIVERY:

EXTERNAL PROBES ARE NOT INCLUDED IN DELIVERY


TEMPERATURE SENSOR - external probe Pt1000  
Measuring range -200 to +600 °C
Accuracy ±0.2 °C (-200 to +100 °C);
±0.2 % from reading
from +100 to +600 °C
Resolution 0.1 °C
TEMPERATURE+HUMIDITY SENSOR - external probe T+RH
DIGI
 
Measuring range according to the connected probe Digi/M
Accuracy according to the connected probe Digi/M
Resolution 0.1 °C
DEW POINT  
Measuring range according to the connected probe Digi/M
Accuracy according to the connected probe Digi/M
Resolution 0.1 °C
CO2 SENSOR  
Measuring range 0 to 2 000 ppm
Accuracy 50 ppm + 2 % of the measured value at 23 °C a 1013
hPa
Resolution 1 ppm
DC VOLTAGE  
Measuring range 0 to 10 V
Accuracy ±10 mV
Resolution better than 100 µV
DC CURRENT  
Measuring range 0 to 20 mA
Accuracy ±20 µA
Resolution better than 0,1 µA
BINARY SIGNAL  
Input voltage for level “switched on”/ <0,4 V/> 2 V
Minimum/maximum input voltage 0 V/+30 V DC
I mpedance of the “switched on”/ < 10 kOhm/> 300 kOhm
COUNTER INPUT  
Range of counter 24 bit (16 777 215) the counter overflow can be
allowed
Maximum input frequency 200 Hz
GENERAL TECHNICAL DATA  
Operating temperature -10 to +60 °C
Channels internal CO2 sensor, 2x external temperature probe or connectable temperature+humidity probe,
2x binary, counter,
voltage and current input
Counted values dew point, absolute humidity, specific humidity,
mixing ratio, specific enthalpy
Memory 1 000 000 values (noncyclic record), 600 000 values
(cyclic record)
Recording interval 1s to 24 hours
Display and alarm refresh each 10 s
Recording mode noncyclic - data logging stops after filling the memory
cyclic
- after filling memory oldest data is
overwritten by new
Available temperature units degrees Celsius, degrees Fahrenheit
Communication interface Ethernet, USB, RS232
Ethernet communication protocols WWW, SNMPv1, XML, DATALINK
Alarm protocols E-Mail
Power AC adapter 230Vac/5Vdc (neccessary for Ethernet
interface)
Battery life 3 - 4 weeks
Protection class IP20
Dimensions (without connectors) 178 x 95 x 37mm, without attached cables
Weight (including batteries) approx. 380 g
Warranty 3 years

Switch To Desktop Version